2, Device installation spacing
(1) Distance between switchgear and other components
When installing circuit breakers, isolating switches, and other switching devices, they should be kept at a certain distance from surrounding devices to facilitate operation and maintenance, while avoiding mutual influence. Generally speaking, the horizontal spacing between circuit breakers and adjacent components should not be less than 20mm, and the vertical spacing should not be less than 30mm. This spacing setting can ensure that operators have enough space to perform switch opening and closing operations, and also ensure that the arc generated by the circuit breaker during circuit breaking will not cause damage to adjacent components. For larger switchgear, such as frame type circuit breakers, due to the potential for significant vibrations during operation, the distance between them and surrounding components needs to be appropriately increased.
(2) Distance between fuses and other components
The distance between the fuse and surrounding components is also required during installation. The melt of a fuse may generate high temperatures and arcing during melting, so a sufficient safety distance should be maintained between it and flammable materials or devices sensitive to high temperatures. It is generally recommended that the horizontal and vertical spacing be no less than 50mm. At the same time, in order to facilitate the replacement operation of the fuse, sufficient space should be reserved around it, usually requiring at least 100mm of space above and on the side of the fuse.
(3) The distance between the busbar and other components
As an important component for transmitting current in the electrical cabinet, the distance between the busbar and other components needs to be strictly controlled. The connection between the busbar and the electrical component terminal should ensure sufficient space to avoid heating caused by poor contact. The spacing between busbars should meet the requirements of electrical clearance and creepage distance. At the same time, the distance between busbars and the outer shell of the electrical cabinet should not be too small, generally not less than 20mm, to prevent damage to the insulation layer caused by collision between busbars and the outer shell due to vibration and other reasons. In addition, to prevent overheating of the busbar, a certain distance should be maintained between the busbar and surrounding heating devices (such as high-power resistors, transformers, etc.), usually not less than 100mm.
(4) Distance between electronic components and other devices
If electronic components such as relays, PLC modules, frequency converters, etc. are included in the electrical cabinet, appropriate distances need to be maintained between these components and other devices. Electronic components are sensitive to electromagnetic interference, so a certain electromagnetic shielding distance should be maintained between them and high current devices (such as contactors, reactors, etc.), generally recommended to be no less than 150mm. At the same time, in order to ensure the normal heat dissipation of electronic components, sufficient ventilation space should be left around them, and the distance between adjacent components should not be less than 20mm, and the heat dissipation holes should not be blocked by other components.